Reconfiguration of Actual Distribution Network with Optimum Power Flow for Loss Reduction
İlker Dursun 1,
Feyzi Karaosmanoğlu 1, and
Nurettin Umurkan 2
1. Bogazici Electricity Distribution Company, İstanbul, Turkey
2. Yildiz Technical University, İstanbul, Turkey
2. Yildiz Technical University, İstanbul, Turkey
Abstract—This study presents loss-reduction on radial electrical distribution system by reconfiguration based on optimum power flow pattern. A real section of distribution network from Istanbul is modeled according to actual load and network data. A new configuration is sought heuristically in order to minimize the interference on the optimum flow pattern. Reconfiguration is performed by closing all switches and consecutively opening the suitable switches carrying the minimum current until the radial system is acquired. Existing configuration and the meshed configuration with all switches closed are analyzed according to load flow calculations. A new network configuration satisfying the voltage and current limitations of the system with reduced losses is proposed for the system.
Index Terms—radial distribution networks, loss reduction, network modeling, optimum power flow, reconfiguration
Cite: İlker Dursun, Feyzi Karaosmanoğlu, and Nurettin Umurkan, "Reconfiguration of Actual Distribution Network with Optimum Power Flow for Loss Reduction," International Journal of Electronics and Electrical Engineering, Vol. 4, No. 1, pp. 56-60, February 2016. doi: 10.18178/ijeee.4.1.56-60
Cite: İlker Dursun, Feyzi Karaosmanoğlu, and Nurettin Umurkan, "Reconfiguration of Actual Distribution Network with Optimum Power Flow for Loss Reduction," International Journal of Electronics and Electrical Engineering, Vol. 4, No. 1, pp. 56-60, February 2016. doi: 10.18178/ijeee.4.1.56-60
Array